| The purpose of this
tutorial is to provide information about the Fieldbus* network so that its
wiring system can be designed and installed for cost-effective and
reliable operation. There are many uses for Fieldbus and many ways it can
be configured. It is not possible to give simple rules for wiring a
Fieldbus that a robot could follow and get optimum results. For this
reason, this guide will first explain how the Fieldbus works so that the
wiring system can be designed intelligently to achieve the best
performance and the most reliable operation with the lowest cost.
(*Fieldbus is defined in
ISA standard 5o.o2, Section 24. There are several types of Fieldbusses
described in that standard. The subject of this guide is referred to as H1
low power signaling and is commonly known as Foundation
Fieldbus.)
Fieldbus is a process
control network used for interconnecting sensors, actuators and control
devices to one another. A common type of Fieldbus configuration is shown
below:

A twisted pair cable,
called the home run connects the control room equipment with a
number of devices in the field, sensors such as pressure
transducers and actuators such as valves. The field devices can be
connected to a common terminal block called the chickenfoot, or
crowsfoot at a field junction box. A terminator (T) is
needed at each end of the Fieldbus cable to allow the twisted pair to
carry digital signals. The Fieldbus cable provides power to the attached
devices. A power conditioner (C) is needed to separate a
conventional power supply from the Fieldbus wiring. The devices use the
shared wiring system to get their power and to send signals to one
another.
Devices can also be
connected along the home run cable with spurs (S). This is
sometimes called daisy-chain wiring.

For control systems that
are limited in size, all the wiring components, power conditioner and
terminators, can be in a single wiring block to form a star
configuration.

The diagrams above show
only three of the many possible Fieldbus configurations. The power supply
and conditioner could be in the field or in a marshaling panel. The
control device could be in the field and only a display terminal could be
in the control room. All these configurations are possible so long as the
basic signal transmission capabilities are provided - a twisted pair
cable, two terminators and a conditioned power supply.
While many devices can be
on a Fieldbus, not all devices in a plant need to be on a single network.
Usually, a control device has connections to several Fieldbus networks
called segments. If the distance to a field device is longer than
can be spanned by a single segment, a repeater is used to boost the
signals to and from the further segment.

Wiring
 Fieldbus uses twisted pair wires. A
twisted pair is used, rather than a pair of parallel wires, to reduce
external noise from getting onto the wires. A shield over the twisted
pairs reduces the noise further. The twisted pair and the shield
combination plus any covering is called a cable. Fieldbus cable is similar
to the type used for existing 4-20 mA device wiring and, in most cases,
existing cable can be used for Fieldbus. For new installations or to get
maximum performance from Fieldbus, twisted-pair cable designed especially
for Fieldbus should be used. The important twisted-pair cable
characteristics are:
|
Wire
Size |
18 AWG (0.8
mm) |
|
Shield |
9o%
coverage |
|
Attenuation |
3 dB/km at 39
kHz |
|
Characteristic
Impedance |
1oo Ohms +/-20% at
31.25 kHz |
Another item to check is
the colors of the twisted pair wires. If possible, to avoid confusion, the
wire colors should match the color convention of existing wiring in the
plant. If installing new cable, the suggested convention is to use blue
for the (-) wire and orange for the (+).
Signal Termination
 When a signal travels on a cable
and encounters a discontinuity, such as a wire short or open, it produces
a reflection. This portion of the signal that echoes from the
discontinuity travels in the opposite direction. The reflection is a form
of noise that distorts the signal A terminator* is used to prevent
a reflection at the ends of a Fieldbus cable. In most networks, the
terminator is simply a resistor whose value is the same as the
characteristic impedance of the wire. Since the Fieldbus cable also
carries power, a simple resistor cannot be used because it would use up
the power intended for the devices. A Fieldbus terminator has a capacitor
in series with the resistor to block the DC voltage but lets the signal
through to the resistor.

*A terminator used to
prevent reflections is different than a wire screw terminal block that is
used to connect wires to each other.
Power Conditioning
 If an ordinary power supply were to
be used to power the Fieldbus, the power supply would absorb signals on
the cable because it would try to maintain a constant voltage level. For
this reason, an ordinary power supply has to be conditioned for Fieldbus.
This is done by putting an inductor between the power supply and the
Fieldbus wiring. The inductor lets the DC power onto the wiring but
prevents signals from going into the power supply.
The inductor together with
the capacitors in the terminators forms a circuit that can "ring" and
disrupt the signals. A resistor is placed in series with the inductor to
stop this ringing. This combination of components is a power
conditioner.

In practice, a real
inductor is not used but an electronic equivalent. The electronic inductor
circuit has the added advantage of limiting the current provided to the
network segment if the cable is shorted.
The voltage supplied to
the Fieldbus cable can be as high as 32 V. The voltage at any device can
be as low as 9 V for the device to operate correctly. A typical Fieldbus
device takes about 20 mA of current from the cable. The Fieldbus is
configured so that one of the wires has a (+) voltage, the other wire has
a (-) voltage and the shield is grounded.
A cable with the orange
wire as plus and the blue wire as minus is shown above. This type of cable
is available from Fieldbus cable manufacturers. Other cables or existing
plant wiring conventions may be different. Regardless of the color
convention, keep the sense of Fieldbus polarity consistent throughout the
plant.
Signals
 The twisted pair cables, the
terminators and the power conditioner work together as a wiring system to
carry signals between Fieldbus devices. Now let's look at how the signals
are transmitted.
There are two ways for a
device to transmit signals onto the cable, the bipolar method and the low
power, unipolar method. Both types of signals can be received by all
devices so there are no compatibility issues. At this writing (1998), the
bipolar signaling appears to be universally used. It works like
this:
A bipolar signaling device
draws power from the cable for its internal operation and it also draws an
additional 10 milli-amps that it "wastes". When this device transmits a
high signal, it turns off this 10 mA. This results in the signal on the
wires going high. When the device transmits a low signal, it draws 20 mA
from the wires. The resulting signal waveform is shown below. Note that
the signal is above and below the non-transmitting voltage
level.

A unipolar signaling
device does not draw any more power from the cable than is necessary for
its internal operation. When this device transmits a low signal, it draws
2o mA from the wires. When the device transmits a high signal, it draws no
power from the wires. The resulting signal waveform is shown below. Note
that the signal is below the non-transmitting voltage level of the
cable.

The peak-to-peak signal
voltage is the same as for bipolar signaling. The advantage of the
unipolar signaling is that it takes 1o mA less current from the cable. The
disadvantage of the unipolar signaling is that it may cause a cable system
that is not properly terminated to ring.
Digital data is sent on
the Fieldbus at a rate of 31.25 kbits/second. Thus, each bit cell
is 32 microseconds long. The digital data, ones and zeros, is
represented as a Manchester signal. A zero is a positive signal
transition in the middle of a bit cell; a one is a negative transition in
the middle of a bit cell. A sequence of Manchester encoded ones and zeros
would look like this:

When a device begins
transmitting, it puts out a preamble, a sequence of 8 bits with
alternating ones and zeros.

This pattern is used by
the receiving devices to get synchronized to bit cell
boundaries.
There are also two
non-data symbols. These are N+ that is a high level during the whole bit
cell and N- that is a low during the whole bit cell. These symbols are
used to make an 8-bit start delimiter that shows where real data
starts and an 8-bit end delimiter that shows where data
transmission stops.

Combining the different
parts, a single transmission from a device, a frame, looks like
this:

The Data portion of the
frame contains information such as the address of the device for which the
frame is intended, identification of the type of frame, measurement
values, etc. The Data portion of a frame can be up to 266 bytes
long.
The delimiters are very
different from any signal pattern that might be in the Data portion of the
frame. This allows the Data portion of the frame to be unambiguously
identified and allows Data corrupted by noise to be detected. This feature
makes Fieldbus much more robust than other control networks.
Because all devices share
the cable, a way must be established for only one device to transmit at a
time. Otherwise, there would be chaos on the cable with all the
transmitted signals interfering with one another. Selecting which device
can transmit is performed by a special device called the Link Active
Scheduler, LAS. The LAS sends out a special frame to each device in
turn to allow it to transmit. If an oscilloscope were used to observe the
signals on the Fieldbus, the display would show frames with gaps of
silence between them. A frame might be one from the LAS asking a device to
transmit data, a device broadcasting its data to other devices, a device
reporting an error condition, etc.

The discussion about how
Fieldbus is used for conveying specific types of information is beyond the
scope of this Wiring Design and Installation Guide.
Now that the basic
characteristics of Fieldbus wiring are known, let's look at what happens
to power and signals on the cables.
Wiring Limitations
 The size of a Fieldbus wiring
system and the number of devices on a network segment are limited by power
distribution, attenuation and signal distortion.
Power
The number of devices on a
Fieldbus segment is limited depending on the voltage of the power supply,
the resistance of the cable and the amount of current drawn by each
device. Consider this example:
- The power supply and
power conditioner output is 20 volts.
- The cable used is 18 GA
and has a resistance of 22 Ohms/km for each conductor. The home run is 1
km long. Therefore, the combined resistance of both wires is 44
Ohms.
- Each device at the
chickenfoot draws 20 mA.
Since the minimum voltage
needed by a device is 9 Volts, there are 20 - 9 = 11 Volts that can be
used up by the cable. The total current that can be supplied at the
chickenfoot is
Voltage / Resistance =
Current
11 Volts / 44 Ohms = 250
mA
Since each device draws 20
mA, the maximum number of devices at the chickenfoot of this example
is:
250 / 20 = 12
devices
The Fieldbus cable can be
tested for power carrying capability by simply shorting out the wires at
one end of the cable and measuring the resistance of both wires with an
ohmmeter at the other end.
The power used by Fieldbus
devices varies by device type and manufacturer. Check the device
specifications to determine the device power requirements. One of the gray
areas of the power specifications is the initial inrush current and the
lift-off voltage. Some devices may use a great deal more current
when they are first turned on and may require more than the 9V minimum
voltage to "lift off" and begin operating. The network power distribution
calculation should be based on the worst-case inrush current and liftoff
voltage numbers. Otherwise the network may not start up when power is
first turned on.
Normally Fieldbus is
powered by 24 volt supplies. The maximum voltage that can be on the
Fieldbus is 32 Volts. Devices can withstand up to +/- 35 Volts without
damage. To keep the maximum voltage on the wiring below this limit, some
Field bus wiring blocks have built-in voltage limiters.
When a number of devices
are on the cable at different places, the power distribution calculation
becomes more involved. Following is an example:

A network is shown with
four devices designated 1 through 4. The network wiring has segments a
through g. The junctions of the segments are at A, B and C. Here are the
facts about the network:
|
Device |
Current Required,
mA |
|
1 |
20 |
|
2 |
25 |
|
3 |
30 |
|
4 |
15 |
|
Segment |
Resistance,
Ω |
|
a |
5 |
|
b |
10 |
|
c |
7 |
|
d |
9 |
|
e |
6 |
|
f |
11 |
|
g |
20 |
From this, the amount of
current in each segment can be calculated. Starting at the devices
furthest from the power source:
|
Segment |
Resistance,
Ω |
Current in
Segment, mA |
|
a |
5 |
20 (due to device
1) |
|
b |
10 |
25 (due to device
2) |
|
c |
7 |
45 (due to devices
1+2) |
|
d |
9 |
30 (due to device
3) |
|
e |
6 |
75 (due to devices
1+2+3) |
|
f |
11 |
15 (due to device
4) |
|
g |
20 |
90 (due to devices
1+2+3+4) |
Because voltage equals
resistance times current, the voltage drop in each segment can be
calculated.
|
Segment
|
Resistance,
Ω
|
Current in
Segment, mA
|
Voltage Drop in
Segment, V |
|
a |
5 |
20 (due to device
1) |
o.1 |
|
b |
10 |
25 (due to device
2) |
0.25 |
|
c |
7 |
45 (due to devices
1+2) |
0.315 |
|
d |
9 |
30 (due to device
3) |
0.27 |
|
e |
6 |
75 (due to devices
1+2+3) |
0.45 |
|
f |
11 |
15 (due to device
4) |
0.165 |
|
g |
20 |
90 (due to devices
1+2+3+4) |
1.8 |
From this, the voltage
drop at each node can be calculated:
|
Node |
Voltage Drop,
V |
|
A |
1.8 (due to segment
g) |
|
Device
4 |
1.965 (due to
segments g + f) |
|
B |
2.25 (due to
segments g + e) |
|
Device
3 |
2.52 (due to
segments g + e + d) |
|
C |
2.565 (due to
segments g + e + c) |
|
Device
2 |
2.815 (due to
segments g + e + c + b) |
|
Device
1 |
2.665 (due to
segments g + e + c + a) |
As the table above
indicates, the largest voltage drop is 2.815 volts at device 2. The
current flowing in segment g is 90 mA. Therefore, the power supply and
conditioner must be able to deliver at least 90 mA. The lowest voltage
that can be at the power supply/conditioner is the 9 volt minimum required
by the devices plus the 2.815 volt drop of the cable segments plus the 1
volt needed for signaling plus a safety margin of, say, 1 volt for a total
of about 14 volts.
Intrinsic safety barriers
can be considered segments in the network with a resistance specified by
their manufacturer. This will be covered in more detail later.
Signal Degradation
Limitations
The length of a Fieldbus
network is limited by what happens to the signals as they travel on the
cable.
Attenuation
As signals travel on a
cable, they become attenuated, that is, get smaller. Attenuation is
measured in units called dB or deciBell. This is
calculated:
dB = 20 log (transmitted
signal amplitude / received signal amplitude)
Cables have attenuation
ratings for a given frequency. The frequency of interest for Fieldbus is
39 kHz. Standard Fieldbus cable has an attenuation of 3 dB/km at 39 kHz or
about 70% of the original signal after 1 Km. If a shorter cable is used,
the attenuation is less. For example, a 500 meter standard Fieldbus cable
would have an attenuation of 1.5 dB.
A Fieldbus transmitter can
have a signal as low as 0.75 volts peak-to-peak. A receiver must be able
to detect a signal as little as 0.15 volts peak-to-peak. This means that
the cable can attenuate the signal by
20 log (0.75 / 0.15) = 14
dB
Since the standard
Fieldbus cable has an attenuation of 3 dB/km, this indicates that the
Fieldbus can be as long as
14 dB / (3 dB/km) = 4.6
km
This distance may be
theoretically possible, but there are other factors that have to be
considered. Signals also become distorted as they travel on the
cable.
Distortion Effects on
Network Size
Shown below are a
transmitted signal and a received signal at the end of a long
cable.

The top signal is ideal in
that the signal fits within the exact bit boundaries, the rise and fall
time of the signal is within the Fieldbus specification and the signal
tops are nearly fiat. At the other end of a cable, the signal is
distorted. Besides being attenuated, the signal does not fit nicely within
the bit boundaries, the rise and fall times are longer and the signal top
is not fiat. This signal distortion is caused by varying characteristic
impedance, spur connection reflections, etc. For this reason, Fieldbus
cable cannot be as long as theoretically possible if only attenuation is a
consideration.
There are many causes for
signal distortion. Spurs on the cable are one source. Although it is not
possible to provide a definitive analysis of the effects of spurs, here
are some guidelines that will help estimate if a particular network will
work or is close to having problems. Consider the network below where the
lengths of the cable segments are shown in meters.

It is not clear in this
network which is the home run cable and which are the spurs. In such a
network, place the terminators as far away from one another as possible.
In this example, they are shown as "T". Consider the cable between the
terminators to be the home run cable. Consider ail other cables segments
as spurs.
Testing of various cable
configurations for signal distortion has shown that spurs up to 300 meters
in length do not present a problem. The issue is to determine the
allowable number of spurs. A way to estimate this is as
follows:
The effect of a spur on
the signal is very similar to that of a capacitor (providing the spur is
less than 30o meters long). As an estimate, the capacitance of Fieldbus
cable is about o.15 nF/meter. In this example, the network can be modeled
as the home-run cable with attached capacitors.

In this model, the home
run cable length is 1o35 meters. The capacitance is calculated from the
total cable length of each spur.
From the measurements of
actual cable, it has been determined that the worst case signal distortion
occurs if all the capacitors are on one end of the home run cable. In this
example this would be modeled as

Again, from cable
measurements it was determined that signal attenuation due to capacitance
is 0.035 dB/nF. In this example, attenuation can be calculated as that
caused by the cable plus that caused by the capacitance:
1035 meters x 3 dB/meter +
55 nF x 0.035 dB/nF = 5 dB
This is well within the 14
dB allowed between the lowest level transmitter and the least sensitive
receiver. There are other signal distortions caused by spurs, but these
are insignificant.
Please note that the
results of measurements of signals on long cables and the analysis of
spurs in the above discussion are different from the recommended network
size and spur lengths in the Fieldbus standard. The standard's
recommendations are much more restrictive and are summarized below. In
case there is a question about signal levels or fidelity, use a Fieldbus
Tester to examine the signals before the network begins operation or
during operation.
The fieldbus standard
contains estimates of how long a Fieldbus cable can be and still get
adequate signal quality. For the standard Fieldbus cable, and some types
of existing cables used for control applications, the limits
are:
|
Cable
Type |
Distance, meters
(feet) |
Characteristic
Impedance |
Resistance,
Ohms/kin |
Atten,
dB/km |
Description |
|
Type A (Standard
Fieldbus) |
19oo
(6270) |
100 |
22 |
3 |
Each twisted pair
has a shield |
|
Type B |
12oo
(396o) |
1oo |
56 |
5 |
Multiple twisted
pairs with overall shield |
|
Type C |
400
(1320) |
Unknown |
132 |
8 |
Multiple twisted
pairs, no shield |
|
Type D |
200
(660) |
Unknown |
20 |
8 |
Multiple conductor
cable, no pairing of wires |
There are also estimates
in the standard for the length of spurs and how many devices can be on
various lengths of cable.
|
Number of
Devices |
Maximum Total Spur
Length |
|
1 – 12 |
120
m |
|
13 –
14 |
90
m |
|
15 –
18 |
60
m |
|
19 –
24 |
30
m |
|
25 –32 |
no spurs allowed;
devices must be attached directly to homerun
cable. |
These are only estimates.
The quality of existing cable may vary a great deal. Some existing cable
may be very good while other cable of the same type may be waterlogged,
have deteriorated insulation or be mechanically damaged. The only real way
to determine if existing cable is suitable for Fieldbus or if new cable
has been installed correctly is to use a Fieldbus Tester.
Cable Testing
 Existing or newly installed cable
should be tested to see that it is capable of carrying Fieldbus
signals.
An ordinary digital
voltmeter can be used to test the resistance between the wire pairs and
the resistance from each wire to the shield. Good cable will have
resistances of 10K Ohms or greater. The resistance of the two wires should
also be measured and noted so that this information can be used in network
design calculations.
The ability of the wire
pair to carry Fieldbus signals can be tested using a Fieldbus Wire Tester.
This consists of two parts - a Transmitter and a Receiver. These are
attached to the opposite ends of the cable to be tested. Lights on the
Receiver indicate if the wire pair is able to carry Fieldbus
signals.
Wiring
Polarity
Wiring polarity is
important because some Fieldbus devices are polarity sensitive and have to
be attached to the wiring in the right way. Wired with the wrong polarity,
a device may short out the network or simply not operate.
Currently, the Fieldbus
standard does not specify the colors of the conductors of the twisted pair
wires nor which wire color should be positive and which should be
negative. However, it has been suggested for new installations that the
(+) wire be orange and the (-) wire be blue and that the fieldbus cable
carry an orange jacket. Existing cables may use many different colors.
Whatever the local choice of polarity colors, it is a good idea that this
be consistent throughout the plant. To make the job of keeping polarities
consistent in the plant, some Fieldbus wiring blocks are clearly labeled
with (+) and (-) polarity designations.
Shield
The purpose of the shield
over the twisted pair wires is to keep out noise that might interfere with
the signals. The shield is most effective if it is connected to ground or
earth at only one place. Otherwise, the shield can carry ground
currents that introduce noise into the twisted pair cable. The cable
shield is generally grounded at the power conditioner or at the intrinsic
safety barrier.
Surge Protection
 The Fieldbus is expected to be used
outdoors. This exposes the wiring to possible lightning strikes or large
currents or voltage surges induced by nearby lightning strikes.
Since the shield is grounded at only one end, it can become a good
lightning conductor into the control room. A way to overcome this problem
is to use a surge suppressor.
The surge suppressor
is a small gas-filled tube that has a very high resistance when the
voltage across it is below 75 Volts. At higher voltages, the gas in the
tube ionizes and produces a very low resistance path to ground. This can
carry the very large currents as long as the voltage surge lasts. Surge
suppressors are built into some Field bus terminators.
Even with surge
suppressors, lightning may induce a large voltage between the wire pair.
To prevent this from damaging the attached devices, a voltage limiter is
placed between the two wires in some Fieldbus terminators.
Intrinsic Safety Barriers
 In some plants, the atmosphere may
be explosive because of volatile gasses or liquids, grain dust, coal dust,
etc. In these situations, all equipment has to be such that it is not hot
enough to ignite the atmosphere and that electrical equipment is such that
under no condition can it produce sparks that can ignite the atmosphere.
These requirements also apply to Fieldbus if it is used in a hazardous
area. An Intrinsic Safety barrier limits the available power to the
Fieldbus to provide this protection. It should be noted that generally no
more than 6 devices can be used on a segment with an IS barrier and
the segment will be reduced in length because the IS barrier reduces the
available power and attenuates the signal.

A detailed discussion of
Intrinsic Safety and the requirements for barriers, cabling and devices is
beyond the scope of this Guide. For more information, contact the Fieldbus
Foundation at 512-794-8890 for Document AG-163, 31.25 kbit/s Intrinsically
Safe Systems.
Wire Connections
 Segments of the wires that make up
the wiring system for a Fieldbus network need to be connected together.
traditionally, this has been done by using terminal strips. For example,
to connect two segments of a home run cable and one device on a spur, the
following connections would have to be made:

While this type of wire
termination works, it has some disadvantages. For example, it is easy to
get mixed up and reverse the polarity of the wires. Also, multiple wires
are fastened under the same screw. This has questionable
reliability.
There are wire termination
blocks that are designed specifically for Fieldbus. These blocks have the
connections between corresponding wire terminations made internally. There
are several methods of terminating the wire to the block - spring clamps,
screw terminals and pluggable connectors. The use of any particular type
depends on how permanent the wiring installation is to be, on preferences
of the installers, and on plant standards.

Preparing the Wiring System
 Test the installed cable before
connecting any other wiring system components or Fieldbus devices to be
sure it meets Fieldbus requirements. Install the terminators, power supply
and power conditioner, any spurs and, if required, the intrinsic safety
barrier.
Provide a substantial
connection, such as a AWG #6 to #10 wire, between the chickenfoot
terminator's ground stud and a good ground. The terminator has surge
protectors built into it. If a nearby lightning strike induces large
voltages on the cable, the surge protectors shunt the unwanted energy to
ground and protect the Fieldbus devices attached to the network. Under
normal conditions, the surge protector does not affect the Fieldbus
operation in any way.
Before connecting the
shield to ground, use an ohmmeter to check that the shield is not
connected to ground or to one of the wires in the cable.
Wiring Practices
 The best designed Fieldbus wiring
system, even one that uses high quality cable and components, will not be
reliable if some care is not taken during installation.
- If multiple homerun
cables go to a field junction box, do not attach the cable shield wires
from different network segments together. This can cause ground loops
and induce noise into the wires.
- Do not ground the
shield of any cable in more than one place.
- At a device, do not
connect the cable shield to the device ground or chassis.
- Use wire strippers that
do not nick the wire as they strip the insulation.
- Use crimp ferrules or
tin the wire ends to prevent stranded wires from getting loose and short
to other wires. There is an added benefit to using crimp ferrules: The
ferrules provide a gas-tight connection between the wire and the ferrule
that is corrosion resistant. The ferrule material is the same as the
wire terminal on the wiring blocks. Similar metals are much more
corrosion resistant than a bare wire in wire terminal.
- Use wiring terminals
that hold the wire ferrule securely and are vibration resistant.
The cable shield should
be grounded at only one point. This is usually at the control room end
of the cable. If an intrinsic safety barrier is used, the cable shield is
grounded at the barrier.
Testing an Operating Network
 Once the Fieldbus network starts
operation, there are several types of network tests that can be
performed.
- The simplest test is to
determine if there is sufficient power on the wiring at each of the
devices. This can be done with an ordinary digital voltmeter. Another
simple test is to use the Receiver part of the Wire Tester to verify the
general signal levels on the network.
- The next level of
testing is to determine what devices are on the network and measure the
signal amplitude of each device. Measuring the noise on the network is
also useful. This is done by using a Network Tester.
- Beyond determining the
health of the signals on the wiring, the information sent by the
different devices to each other can be examined. This is done by using a
computer that runs an analysis program. The computer acquires all frames
on the network and shows their sequence on the screen. Discussion of
protocol testing is beyond the scope of this Guide.
Generally, once a control
network is operating properly, the Fieldbus communications protocols do
not break. Wiring, on the other hand, can deteriorate or be damaged in a
number of ways. Having the capability to identify a wiring problem and to
determine its location is very useful.
|